FreeAvailable now — free

Voltage Drop Calculator — Volts and Percent

Estimate circuit voltage drop.

Project & Input Data

Phase

Your project criterion: enter the value from your governing code, specification or approved supplier data. No standard value is assumed.

Your project criterion: enter the value from your governing code, specification or approved supplier data. No standard value is assumed.

%

Your project criterion: enter the value from your governing code, specification or approved supplier data. No standard value is assumed.

Embedded standards & references

  • Schneider Electrical Installation Guide P/S, voltage-drop and Q correction relations; not cable selection

Results are engineering aids and require verification by a qualified professional before use on a real project.

Engineering Assumptions

Direct calculation — Single sinusoidal circuit with lagging load

  • Three-phase voltage is line-to-line with balanced sinusoidal load and lagging displacement factor. Power input is electrical, not mechanical output. No imbalance, harmonics or motor-efficiency model. Independent S is not merged with P/PF.
  • Voltage drop is approximate using operating-temperature resistance and path reactance from product data, with one-way length. No assumed temperature correction, ampacity or protection. Capacitors are Q arithmetic only, no stage/resonance selection; a target below existing PF gives zero correction, not reduced PF.
  • Water pressure is one path at actual internal diameter, water1000kg/m³ and g=9.80665. Hazen-Williams is empirical for water, not all fluids. Elevation is signed. Equivalent lengths and devices must not be duplicated. Compare at the same flow/pressure; no pump or fire-network approval.
  • Density×area demand does not simulate actual sprinkler overdischarge or balancing. Density/area/hose values require project evidence; defaults are examples, not rules. Comparison success is not conformity certification.
  • https://www.electrical-installation.org/enwiki/Calculation_of_voltage_drop_in_steady_load_conditions
  • https://www.electrical-installation.org/enwiki/How_to_calculate_the_level_of_reactive_energy_compensation
  • https://www.epa.gov/water-research/epanet

Formula Summary

  • ΔV≈kIL(Rcosφ+Xsinφ)/1000; k=2(single),√3(balanced three)
  • R at operating temperature; one-way L; three-phase voltage is line-to-line

Built-in definitions, not code limits

DefinitionValue
SingleI:1;ΔV:2
Balanced three√3
Power triangleS²=P²+Q²

SI constants and declared engineering relations

Results

Enter your data and press Calculate to see the results.

Engineering Insight

Keep measurements and independent inputs separate from the calculated identity; results neither design equipment nor certify conformity.

Recommended Action

Document P/S, R/X or C and pipe diameter sources; check the same operating conditions before engineering review.

Voltage drop decides whether a cable run is acceptable long before ampacity does on long circuits. Enter the design current, the one-way run length and the cable resistance per kilometre from your manufacturer data, and compare the result with the percentage limit you have adopted for the installation.

Method and assumptions

Single sinusoidal circuit with lagging load

  • ΔV≈kIL(Rcosφ+Xsinφ)/1000; k=2(single),√3(balanced three)
  • R at operating temperature; one-way L; three-phase voltage is line-to-line
  • Three-phase voltage is line-to-line with balanced sinusoidal load and lagging displacement factor. Power input is electrical, not mechanical output. No imbalance, harmonics or motor-efficiency model. Independent S is not merged with P/PF.
  • Voltage drop is approximate using operating-temperature resistance and path reactance from product data, with one-way length. No assumed temperature correction, ampacity or protection. Capacitors are Q arithmetic only, no stage/resonance selection; a target below existing PF gives zero correction, not reduced PF.
  • Water pressure is one path at actual internal diameter, water1000kg/m³ and g=9.80665. Hazen-Williams is empirical for water, not all fluids. Elevation is signed. Equivalent lengths and devices must not be duplicated. Compare at the same flow/pressure; no pump or fire-network approval.
  • Density×area demand does not simulate actual sprinkler overdischarge or balancing. Density/area/hose values require project evidence; defaults are examples, not rules. Comparison success is not conformity certification.
  • https://www.electrical-installation.org/enwiki/Calculation_of_voltage_drop_in_steady_load_conditions
  • https://www.electrical-installation.org/enwiki/How_to_calculate_the_level_of_reactive_energy_compensation
  • https://www.epa.gov/water-research/epanet

Worked example

A 63 A three-phase feeder, 55 m long, on a cable of 0.727 Ω/km, checked against a 3% limit on 400 V.

Worked example results
ResultValue
Path coefficient Rcosφ+Xsinφ0.73 Ω/km
Approximate lagging-load voltage drop4.36 V
Drop as base-voltage percentage1.09 %
Remaining budget in percentage points1.91 %
Approximate receiving voltage, not load flow395.64 V

These figures are produced by the same calculator engine used on this page.

Frequently asked questions

Where do I get resistance per km?
From the cable manufacturer's data for the conductor material, size and operating temperature. The tool has no cable table and assumes no value.
Is reactance considered?
No. The equation is resistive only (ΔV = k·I·L·R ÷ 1000). For large cables where reactance matters, use an impedance-based method.
Which percentage limit applies?
The allowable percentage is a project/regulatory criterion you enter. Alasos does not claim compliance with any electrical code.

Next step and related links

Free calculators are open to everyone, and CSV export is free for everyone too. Project saving and PDF/Excel reports come with Professional, and integrated workflows with Premium.