Electrical Load Estimate
Estimate project electrical loads.
Electrical Design SuiteStep 1 of 6
This calculator is part of a paid level
Unlock this calculator with a single purchase; access stays on your account for life.
Early-stage projects need a defensible load figure before the detailed schedules exist. This Professional calculator assembles one from inputs you control: area × load density gives the connected load, additional loads are added, diversity reduces it to a demand load, spare capacity is applied, and power factor converts the result to kVA for transformer or generator discussions.
Method and assumptions
Grouped ku/ks load schedule and vector P/Q
- Pconnected=Σn×input kW; Qconnected=ΣP×tan(acos(PF))
- Pgroup=ks×Σ(P×ku); Qgroup=ks×Σ(Q×ku); sum independent groups
- S=√(ΣP²+ΣQ²); apply spare once after demand; I=1000S/(√3V)
- https://www.electrical-installation.org/enwiki/Estimation_of_actual_maximum_kVA_demand
- ku applies to each load, one consistent ks per nonoverlapping group; no extra upstream ks. Online guide is not an international code table; defaults are examples, not approved factors.
- Electrical input and fixed sinusoidal lagging PF at utilized load, balanced three-phase. Harmonics, neutral/single-phase/capacitor/motor-start and NEC/IEC compliance excluded; no automatic feeder/transformer selection.
Frequently asked questions
- Where does the load density come from?
- From your own load study or the governing requirement for the building type. The engine stores no W/m² table and applies no default figure on your behalf.
- How are diversity and spare capacity applied?
- Diversity is a percentage of the connected load, and spare capacity is then added on top of that demand figure, so the two never compound in the wrong order.
- Can it replace a design load schedule?
- No. It is a preliminary decision-support estimate. Final distribution, protection and sizing must come from an approved design reviewed by a competent engineer.
- Why does the tool need power factor?
- Because supply equipment is rated in kVA. The demand in kW is divided by the power factor you enter to express the same load in kVA.
- Is this calculator free?
- It sits in the Professional level. The method and inputs are documented openly here so you can judge the fit before unlocking it.